气灭盘故障(5.19-5.22)
2024-05-01 19:07
views:
236
source:
维修调度
(4号线)22:55时,中央综合监控系统显示城门综合监控室气灭盘气体释放,OCC通知自动化专业。
22:59时,经确认,现场无火情,气体实际无释放。[二类信息](前发信息故障时间有误,以此条信息为准)
(4月15日4号线城门气灭盘显示气体释放故障跟进)05:42时,自动化专业回复:故障原因为气瓶间内启动瓶上方防
火泥的油水混合物滴落到压力开关接线端子,导致综合监控设备室气灭盘短路,气体释放反馈灯亮。已将气灭管路处防火泥及
接线端子内油水混合物清除,经观察,设备正常运行,故障消除。[二类信息]
(4号线)12:40时,中央综合监控系统显示城门综合监控室气灭盘气体释放,OCC通知自动化专业。
12:43时,经确认,现场无火情,气体实际无释放。[三类信息]
(4号线城门综合监控室气灭盘气体释放故障跟进)12:49时,自动化专业回复:故障原因待查,现场已安排人员值守。
[三类信息]
Disclaimer: The above articles are added by users themselves and are only for typing and communication purposes. They do not represent the views of this website, and this website does not assume any legal responsibility. This statement is hereby made! If there is any infringement of your rights, please contact us promptly to delete it.